Description
The Flex-Core FCL-R411 series is a flexible split-core current transformer which was designed for easy installation on large bus or wire conductors in order to make electrical load surveys or for continuous monitoring of current. The FCL-R411 series features a flexible core which is constructed from directional silicon steel. The secondary windings are made up of copper. The FCL-R411 series is also encapsulated in silicon rubber which protects against moisture, dirt, oil and corona.
The FCL-R411 series also features a 0.72 kV BIL (10 kV Full Wave) insulation level, a thermal factor of 1.25 at 30°C (86°F) & 1.0 at 55°C (131°F) and 12 ft. leads with spade connectors. The FCL-R411 flexible split-core current transformers are also UL-rated and meet IEC 60044-1 standards.
Features:
- Flexible core for easy installation on bus bars & conductors
- For use with any 5 Amp indicating or recording ammeter or Amp or Watt Transducer
- 12 Ft. Secondary Leads with spade connectors
- 4.00″ x 11.00″ Rectangular Window Diameter
- Accuracy:
- 200:5A to 300:5A – 4%
- 400:5A to 500:5A – 3%
- 600:5A to 800:5A – 2%
- 1000:5A to 6000:5A – 1%
- Insulation Level: 0.72 kV BIL (10 kV Full Wave)
- Thermal Factor: 1.25 at 30°C (86°F) & 1.0 at 55°C (131°F)
- Operating Temperature: -45°C to +55°C (-49°F to 131°F)
- UL Recognized and meets IEC 60044-1 standard
Applications:
- 5 Amp Indicating Ammeters
- Watt Transducer
- Current Transducer
- KWH Meter
- Demand Meter
- Power Factor Meter
- Current Sensing Relays
- Energy Management Systems